Your Position:Home > Products Center > 胜利仪器 > VICTOR 1601 Wireless High Voltage Nuclear Phase Detector Voice Nuclear Phase Detector

  • VICTOR 1601 Wireless High Voltage Nuclear Phase Detector Voice Nuclear Phase Detector

    Model:VICTOR 1601

    Brand:胜利仪器

    Introduction:VICTOR 1601 all-intelligent wireless high and low voltage nuclear phase meter, also known as all-intelligent wireless high voltage speech nuclear phase meter, wireless high voltage nuclear phase meter, referred to as nuclear phase meter or nuclear phase meter, is composed of wireless receiver, XY detector, telescopic insulation rod, etc.

  • Technical specifications

    Work Can

    Wireless high and low voltage speech nuclear phase, frequency, phase, phase sequence, electrical test

    Electricity source

    DC 3.7V rechargeable lithium battery,USB charging interface, continuous operation for about 10 hours

    Transmission mode

    315MHz,433MHz wireless transmission

    Nuclear phase distance

    The distance is about 150 meters

    Disy mode

    3.5 "true color LCD disy

    Measuring range

    Nuclear phase voltage level: AC 10V ~ 550kV

    Phase: 0.0° ~ 360.0°

    Frequency: 45Hz to 75Hz

    Resolution rate

    0.1°;0.1Hz

    Precision

    Phase: ≤±10° (23℃±5℃,80percentRH below)

    Frequency: ≤±2Hz (23℃±5℃,80percentRH below)

    Phase differentiation

    In phase :-30° ~ 30°; Out of phase: 90° ~ 150° and 210° ~ 270°

    语音Work能

    同相、异相、X信号正常、Y信号正常等语音Work能

    Insulation rod size

    After stretching, the length is about 3.2m. The length after contraction is about 0.6m

    Data storage

    Group 9999

    Nuclear phase mode

    Contact nuclear phase: the bare conductor below 35kV, or the conductor with safety insulation skin below 110kV directly contact the nuclear phase (with insulated rod operation)

    Non-contact core phase: bare conductor above 35kV, or line above 110kV adopts non-contact core phase (with insulated rod operation)

    Electrical instruction

    Detector "toot toot toot" beep

    Shift gears

    Automatic shift

    Sampling rate

    2 times per second

    Instrument size

    Detector: Length width and thickness 145mm×60mm×48mm

    Receiver: Length and width 250mm×100mm×40mm

    Backlight control

    Press the up and down arrow keys to adjust the backlight brightness

    Induction intensity control

    According to the induced electric field intensity, the detector can automatically control the magnification, which is convenient for the nuclear phase in dense ces

    Data retention

    Press the HOLD key to HOLD data in test mode, then press the Hold key to cancel hold

    退出Work能

    按ESC键退出当前Work能界面,返回上级目录

    Data retrieval

    按ENTER进入Data retrieval模式后,按箭头键翻阅存数据

    No signal indication

    The "----" symbol is disyed dynamically when the receiver does not receive the transmitted signal

    Automatic shutdown

    开机约15分钟后,仪表Automatic shutdown,以降低电池消耗

    电池电压

    When the battery voltage is lower than 3.2V:
    Detector: The power indicator blinks slowly to remind charging;
    Receiving end: battery low voltage symbol disy, remind to charge

    Rated current

    Detector: 35mA max; Receiver: 300mA max

    Instrument quality

    Detector: 205g(including battery)

    Receiver: 395g(including battery)

    Insulation rod: 1.45kg

    Total mass: 9.8kg(including instrument box)

    Working temperature and humidity

    -10℃ ~ 40℃; 80percentRh below

    Storage temperature and humidity

    -10℃ ~ 60℃; 70percentRh below

    Interference

    No extra-strong electromagnetic field; No 433MHz,315MHz simultaneous interference

    Insulation strength

    Insulation rod: AC 110kV/rms(5 sections of insulation rod after stretching, between the ends)

    Detector: 2000V/rms(between the two ends of the housing)

    Receiver: 2000V/rms(between the ends of the housing)

    Structure

    Drip-proof type II,IP63

    Suitable for safety rules

    GB13398-92, GB31.1-311.6-8,3DL408-91 standard and the national newly issued power industry standard "1kV ~ 35kV portable nuclear phaser general technical conditions DL/T971-2005" requirements

    Comply with IEC61481-A2:2004; IEC 61243-1 ed.2:2003 Standard