testo 480 multifunctional detector
-- Expert in air-conditioning and ventilation system debugging, environmental comfort testing
Product Introduction:
testo 480 can record temperature, humidity, wind speed, illumination, thermal radiation, turbulence, carbon dioxide and other parameters. It is the latest multifunctional measurement instrument for air conditioning systems and indoor environment detection in office buildings, residential and industrial buildings. For the HVAC industry system optimization experts, technical service providers and engineers to provide a complete overall solution support
testo 480's intelligent calibration function allows customers to measure and operate more freely, more professional!
Automatic reminder of calibration time
With the latest digital memory probe, the probe with storage core will automatically remember the instrument and calibration information, will automatically remind the customer "your instrument and probe should be calibrated", to ensure that your instrument is always accurate and reliable!
The probe automatically compensates for calibration deviation
After the user enters all calibration data through the software, the data will be permanently stored in the probe. When used by customers, the probe will automatically compensate for calibration deviation, to achieve zero error data disy
The probe calibration can be realized without the host
The digital memory probe makes the calibration process easier and more convenient. If the air conditioning engineer needs to calibrate, there is no need to send the host to the calibration mechanism, only the probe can complete the calibration work, your instrument can continue your other measurements. At the same time, the system precision includes the host and the probe, ensuring the reliability and repeatability of the measurement results
Advantages at a glance:
Digital memory probe, no host can be calibrated probe
Automatically compensates calibration deviation and automatically reminds the probe of calibration time
Built-in grille measurement method, easy to achieve standard ventilation system measurement
Support SD card and USB data transmission, professional software analysis
The new touch button is easier to control
Technical data |
|
---|---|
Probe interface |
2 K type thermocouple interfaces 1 built-in differential pressure interface 3个数字式Probe interface |
Other connections |
USB port,SD card, power supply, infrared port for connecting fast printers |
Operating temperature | 0 ~ 40 °C |
External power supply |
Connecting the power supply can realize long-term measurement and battery charging |
Battery life |
8 hours (host, no probe,50percent disy brightness) |
Show |
彩色图形Show |
Memory |
The memory can store 10,000 measurement reports |
Built-in measurement parameters
|
|
---|---|
Type K thermocouple | Range: -200 ~ 1370 °C Accuracy: ± (0.3 °C 0.1percent of the measured value) Resolution: 0.1 °C |
Differential pressure |
Range: -25 ~ 25 hPa Accuracy: ± (0.3 Pa 1percent of the measured value) Resolution: 0.1 Pa |
Absolute pressure | Range: 700 ~ 1100 hPa Accuracy: ± 3 hPa Resolution: 0.1hPa |
External wind speed probe
| 量程 | 精度(±1数位) |
---|---|---|
0635 9542 Impeller type wind speed probe The diameter is 16mm |
+ 0.4 ~ + 50 m/s - 10 °C ~ + 70 °C
|
±(0.2m /s 1percent)(0.4~40m/s) ±(0.2m /s 2percent)(40~50m/s) ± 1.8 °C |
0635 1543 Thermal wind speed probe 90 degree bend |
0 ~ + 20 m/s - 20 ~ + 70 °C 0 ~ 100 %RH |
± (0.03 m/s 4percent)
|
0635 9343 Impeller type wind speed probe Diameter 100mm |
+ 0.10 ~ + 15 m/s
|
± (0.1 m/s 1.5percent of the measured value)
|
External comfort probe
| 量程 | 精度(±1数位) |
---|---|---|
0636 9743 Temperature and humidity probe Diameter 12mm |
0 ~ 100 %RH
- 20 ~ + 70 °C |
± (1.0 percentRH 0.7percent) (0 ~ 90 percentRH)
± (1.4 percentRH 0.7percent) (90 ~ 100 percentRH) ± 0.5 °C |
0632 1543 IAQ Indoor Air Quality Probe |
- 20 ~ + 70 °C
|
± 0.5 °C
|
0628 0143 Turbulence probe |
0 ~ + 50 °C
|
± 0.5 °C
|
0602 0743 Thermal radiation Black Scout Head Diameter 150mm |
0 ~ + 120 °C |
Level 1 accuracy |
0635 0543 Illuminance probe |
0 ~ 100,000 Lux |
Grade C according to DIN 5032-7
|
External temperature probe
| 量程 | 精度(±1数位) |
---|---|---|
0602 1793 空气探头,Type K thermocouple |
- 60 ~ + 400 °C
|
Level 2 precision |
0602 0393 表面探头,Type K thermocouple Fast response with spring-loaded surface probe |
- 60 ~ + 300 °C |
Level 2 precision |
0602 1293 Waterproof, dip/insert probe Type K thermocouple |
- 60 ~ + 400 °C |
± 0.2 °C(-20 ~ +70 °C )
|
0614 0073 Pt 100 High precision, immersion/insert probe 3 mm diameter |
- 100 ~ + 400 °C |
± 0.15 °C 0.2percent (-100 ~ -0.01 °C)
|